If you're looking for help fixing your Ruud Air Conditioner, look no further! Our comprehensive Ruud Air Conditioner Troubleshooting guide will explain common issues, provide tips, and show you how to read your model's error codes.

Symptom: Unit will not run 

Possible Cause: 
Power off or loose electrical connection 
Thermostat out of calibration-set too high 
Defective contactor 
Blown fuses 
Transformer defective 
High pressure control open (if provided) 
Interconnecting low voltage wiring damaged 

Remedy: 
Check for correct voltage at compressor contactor in control box 
Reset 
Check for 24 volts at contactor coil – replace if contacts are open 
Replace fuses 
Check wiring-replace transformer 
Reset-also see high head pressure remedy-The high pressure control opens at 610 PSIG 
Replace thermostat wiring 
Symptom: Condenser fan runs, compressor doesn’t 

Possible Cause: 
Run or start capacitor defective (single phase only) 
Start relay defective (single phase only) 
Loose connection 
Compressor stuck, grounded or open motor winding. open internal overload 
Low voltage condition 
Low voltage condition 

Remedy: 
Replace 
Replace 
Check for correct voltage at compressor – check & tighten all connections 
Wait at least 2 hours for overload to reset. If still open, replace the compressor. 
At compressor terminals, voltage must be within 10% of rating plate volts when unit is operating. 
Add start kit components. 
Symptom: Insufficient cooling 

Possible Cause: 
Improperly sized unit 
Improper airflow 
Incorrect refrigerant charge 
Air, non-condensibles or moisture in system 
Incorrect voltage 

Remedy: 
Recalculate load 
Check – should be approximately 400 CFM per ton. 
Charge per procedure attached to unit service panel 
Recover refrigerant, evacuate & recharge, add filter drier 
At compressor terminals, voltage must be within 10% of rating plate volts when unit is operating. 
Symptom: Compressor short cycles 

Possible Cause: 
Incorrect voltage 
Defective overload protector 
Refrigerant undercharge 

Remedy: 
At compressor terminals, voltage must be ± 10% of nameplate marking when unit is operating. 
Replace – check for correct voltage 
Add refrigerant 
Symptom: Registers sweat 

Possible Cause: Low evaporator airflow 
Remedy: Increase speed of blower or reduce restriction – replace air filter 

Symptom: High head-low vapor pressures 

Possible Cause: 
Restriction in liquid line, expansion device or filter drier 
Flow check piston size too small 
Incorrect capillary tubes 
TXV does not open 

Remedy: 
Remove or replace defective component 
Change to correct size piston 
Change coil assembly 
Replace TXV 
Symptom: High head-high or normal vapor pressure – Cooling mode 

Possible Cause: 
Dirty condenser coil 
Refrigerant overcharge 
Condenser fan not running 
Air or non-condensibles in system 

Remedy: 
Clean coil 
Correct system charge 
Repair or replace 
Recover refrigerant, evacuate & recharge 
Symptom: Low head-high vapor pressures 

Possible Cause: 
Flow check piston size too large 
Defective Compressor valves 
Incorrect capillary tubes 

Remedy: 
Change to correct size piston 
Replace compressor 
Replace coil assembly 
Symptom: Low vapor – cool compressor – iced evaporator coil 

Possible Cause: 
Low evaporator airflow 
Operating below 65°F outdoors 
Moisture in system 
TXV limiting refrigerant flow 

Remedy: 
Increase speed of blower or reduce restriction – replace air filter 
Add Low Ambient Kit 
Recover refrigerant – evacuate & recharge – add filter drier 
Replace TXV 

Symptom: High vapor pressure 

Possible Cause: 
Excessive load 
Defective compressor 

Remedy: 
Recheck load calculation 
Replace 

Symptom: Fluctuating head & vapor pressures 

Possible Cause: 
TXV hunting 
Air or non-condensibles in system 

Remedy: 
Check TXV bulb clamp – check air distribution on coil – replace TXV 
Recover refrigerant, evacuate & recharge 

Symptom: Gurgle or pulsing noise at expansion device or liquid line 

Possible Cause: Air or non-condensibles in system 
Remedy: Recover refrigerant, evacuate & recharge



Related Error Code Pages:
Ruud Air Conditioner Error Codes, Ruud Furnace Error Codes, Ruud Water Heater Error Codes, Ruud Heat Pump Error Codes,

Related Troubleshooting Pages:
Ruud Air Conditioner Troubleshooting, Ruud Furnace Troubleshooting, Ruud Water Heater Troubleshooting, Ruud Heat Pump Troubleshooting,

Related Repair Pages:
Ruud Air Conditioner Repairs, Ruud Furnace Repairs, Ruud Water Heater Repairs, Ruud Heat Pump Repairs,

Related Parts Pages:
Ruud Air Conditioner Parts, Ruud Furnace Parts, Ruud Water Heater Parts, Ruud Heat Pump Parts,

Related Price Pages:
Ruud Air Conditioner Prices, Ruud Furnace Prices, Ruud Water Heater Prices, Ruud Heat Pump Prices,

Related Pages:
local ac services, heating and cooling, home ac service, residential air conditioner repair, air conditioner,


Ruud Air Conditioner Troubleshooting

Ruud Air Conditioner problems

Ruud Air Conditioner broken

Ruud Air Conditioner issue

Ruud Air Conditioner difficulty


Product Reviews:

The temperatures can really go high in the summer days. You can’t imagine
The temperatures can really go high in the summer days. You can’t imagine my frustration when my AC broke last summer. For about 2 weeks we had to go without any air conditioning. I was in a rush to get the problem fixed so I got this Ruud but I didn’t know much about the unit. Finally, the problem was solved but then I wasn’t sure the unit would hold up without breaking down. So far so good, haven’t had to do anything except routine maintenance.
Published: September 6, 2020
pickhvac.com Pompano Beach, FL
Source: pickhvac.com

Things are going well so far. I haven’t had any trouble with the Ruud AC
Things are going well so far. I haven’t had any trouble with the Ruud AC I bought. I got it 5 months ago to replace the old one which couldn’t cool the house anymore. Thanks to Ruud and a nice dealer here, I can enjoy the comfort of my home.
Published: November 6, 2020
pickhvac.com Modesto, CA
Source: pickhvac.com

We have had the same ac unit for the last 18 years. After such a long time
We have had the same ac unit for the last 18 years. After such a long time a replacement is usually a better bargain than repairing. So we went ahead and bought this Ruud. I like how quiet it runs. It functions perfectly and does take much to run so the utility bill is low. This is what good manufacturing is all about.
Published: August 6, 2020
pickhvac.com Albany, GA
Source: pickhvac.com

Features that make an air conditioner perform well and last long are in eac
Features that make an air conditioner perform well and last long are in each unit that Ruud makes, no matter the level. Quality matters to Ruud, so every system has optimized access ports for servicing, powder coated paint and rust-resistant screws. They also have an excellent SEER rating, and no unit is below 15.5.
Published: December 6, 2019
furnaceprices.ca
Source: furnaceprices.ca

Hurray for Ruud. I’m so happy this turned out great. I was skeptical abou
Hurray for Ruud. I’m so happy this turned out great. I was skeptical about replacing my air conditioner because the online reviews gave me the impression that there is nothing really worth the trouble out there. I got this Ruud because a friend of mine reassured me of its excellent services. For 7 months now the unit hasn’t given me any problems. Only had to fix it once and that was covered by the warranty.
Published: October 6, 2020
pickhvac.com Tyler, TX
Source: pickhvac.com

Visa MasterCard

Site Secured By The Website Guardian
TOP